Danfoss ECL Comfort 310 Installation Manual page 25

Application a376
Hide thumbs Also See for ECL Comfort 310:
Table of Contents

Advertisement

Installation Guide
A376.3:
Description
Terminal
19
Phase for alarm output
18
Alarm
17
Not to be used
16
Not to be used
15
Not to be used
14
Phase for circulation pumps
13
P3
Heating circulation pump, ON / OFF, circuit 2
12
P2
Heating circulation pump, ON / OFF, circuit 1
11
P1
DHW circulation pump, ON / OFF, circuit 3
10
Supply voltage 230 V a.c. - neutral (N)
9
Supply voltage 230 V a.c. - live (L)
8
Not to be used
7
Not to be used
6
Not to be used
5
Not to be used
4
Not to be used
3
Not to be used
2
Not to be used
1
Not to be used
* Relay contacts: 4 A for ohmic load, 2 A for inductive load
Factory established jumpers:
5 to 8, 9 to 14, L to 5 and L to 9, N to 10
Danfoss District Energy
ECL Comfort 310, application A376
VI.GU.B1.02
Max. load
4 (2) A / 230 V a.c.*
4 (2) A / 230 V a.c.*
4 (2) A / 230 V a.c.*
4 (2) A / 230 V a.c.*
DEN-SMT/DK
25