Flow / Power Limit - Danfoss ECL Comfort 310 Installation Manual

Application a376
Hide thumbs Also See for ECL Comfort 310:
Table of Contents

Advertisement

Installation Guide

7.3 Flow / power limit

Please see the explanation for flow and power limit in circuit 1.
At DHW heating the flow / power limit can be set to a fixed value.
Actual (actual flow or power)
Circuit
3
The value is the actual flow or power based on the signal from flow / energy
meter.
Limit (limitation value)
Circuit
3
Set the limitation value.
Adapt. time (adaptation time)
Circuit
3
Controls how fast the flow / power limitation adapts to the desired
limitation.
OFF:
The control function is not influenced by the 'Adapt.
time' .
1:
The desired temperature is adapted quickly..
50:
The desired temperature is adapted slowly..
If the 'Adapt. time' is too low, there is a risk of unstable control.
130
DEN-SMT/DK
ECL Comfort 310, application A376
13110
Setting range
Factory setting
Read-out only
13111
Setting range
Factory setting
0.0 ... 999.9 l/h
999.9 l/h
13112
Factory setting
Setting range
OFF / 1 ... 50 s
OFF
Flow / power
limitation
Desired flow
temp.
VI.GU.B1.02
Limit
Time
Danfoss District Energy