Alarm - Danfoss ECL Comfort 210 Installation Manual

Application a275 / a375
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide

6.9 Alarm

Alarm for monitoring the flow temperature is only available in
circuit 2 in A275.3 and A375.3 applications.
Many applications in the ECL Comfort 210 and 310 series have an
alarm function. The alarm function typically activates relay 4 (ECL
Comfort 210) or relay 6 (ECL Comfort 310).
The alarm relay can activate a lamp, a horn, an input to an alarm
transmitting device etc.
The relay in question is activated as long as the alarm condition
is present.
Typical alarms:
Actual flow temperature differs from the desired flow
temperature.
6.9.1 Temp. monitor.
Upper difference
Circuit
2
The alarm is activated if the actual flow temperature increases more than
the set difference (acceptable temperature difference above the desired
flow temperature). See also 'Delay'.
OFF:
The alarm function is not active.
1 ... 30 K: The alarm function is active if the actual temperature
gets above the acceptable difference.
Lower difference
Circuit
2
The alarm is activated if the actual flow temperature decreases more than
the set difference (acceptable temperature difference below the desired
flow temperature). See also 'Delay'.
OFF:
The alarm function is not active.
1 ... 30 K: The alarm function is active if the actual temperature
gets below the acceptable difference.
146
DEN-SMT/DK
ECL Comfort 210 / 310, application A275 / A375
12147
Setting range
Factory setting
OFF / 1 ... 30 K
OFF
12148
Setting range
Factory setting
OFF / 1 ... 30 K
OFF
Flow temp. °C
Flow temp. °C
VI.GU.L1.02
Upper difference (set
value)
Desired flow temp.
Time
Lower difference (set
value)
Desired flow temp.
Time
Danfoss District Energy