Settings Overview - Danfoss ECL Comfort 210 Installation Manual

Application a275 / a375
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide

4.0 Settings overview

It is recommendable to make a note of any changed settings in the empty columns.
Setting
Heat curve
Temp. max. (flow temp. limit, max.)
Temp. min. (flow temp. limit, min.)
Ext. desired T — (ECL Comfort 310)
Infl. - max. (room temp. limitation, max.)
Infl. - min. (room temp. limitation, min.)
Adapt. time (adaption time)
High T out X1 (return temp. limitation, high limit, X-axis)
Low limit Y1 (return temp. limitation, low limit, Y-axis)
Low T out X2 (return temp. limitation, low limit, X-axis)
High limit Y2 (return temp. limitation, high limit, Y-axis)
Infl. - max. (return temp. limitation - max. influence)
Infl. - min. (return temp. limitation - min. influence)
Adapt. time (adaptation time)
Priority (priority for return temp. limitation)
Auto saving (saving temp. dependent on outdoor temp.)
Boost
Optimizer (optimizing time constant)
Pre-stop (optimized stop time)
Based on (optimization based on room / outdoor temp.)
Total stop
Cut-out (limit for heating cut-out)
Difference
Max. T limit
Min. ON time
Sequence type (A375 applications)
Stop at T out
Protection
Band limit (A375 applications)
Reaction, o. band (outside band) (A375 applications)
Reaction, in band (A375 applications)
Steps (A375 applications)
ECA addr. (choice of Remote Control Unit)
Demand offset
P demand
Send desired T
P exercise (pump exercise)
P frost T
P heat T (heat demand)
P post-run
Frost pr. T (frost protection temperature)
100
DEN-SMT/DK
ECL Comfort 210 / 310, application A275 / A375
ID
11178
11177
11182
11183
11015
11031
11032
11033
11034
11035
11036
11037
11085
11011
11012
11014
11026
11020
11021
11179
11046
11049
11071
11072
11038
11047
11048
11074
11075
11073
11010
11017
11050
11500
11022
11077
11078
11040
11093
Page
Factory settings in circuit(s)
1
2
103
1.0
104
90 °C
104
10 °C
105
106
-4.0
107
0.0
107
OFF
108
15 °C
108
40 °C
108
-15 °C
109
60 °C
109
0.0
109
0.0
109
25 s
110
OFF
111
-15 °C
111
OFF
112
OFF
112
ON
113
OUT
113
OFF
113
20 °C
114
8 K
114
90 °C
114
0 m
115
3
115
OFF
116
OFF
116
20 K
117
60 s
118
120 s
118
1
119
OFF
119
OFF
119
OFF
119
OFF
120
ON
120
2 °C
120
20 °C
120
3 m
120
10 °C
VI.GU.L1.02
3
Danfoss District Energy

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecl comfort 310