Circuit
1
Choose the input for 'Ext. input' (external override). By means of a switch the
controller can be overridden to Comfort or Saving mode.
OFF:
No inputs have been selected for external override.
S1 ... S8: Input selected for external override.
If S1...S6 is chosen as override input, the override switch must have
gold-plated contacts.
If S7 or S8 is chosen as override input, the override switch can be a
standard contact.
See the drawing for a connection example of an override switch
to input S8.

Danfoss District Energy

ECL Comfort 210 / 310, application A275 / A375
11141
Setting range
Factory setting
OFF / S1 ... S8
OFF
Choose only an unused input for override. If an already used input is
applied for override, the functionality of this input is also neglected.
See also 'Ext. mode' .
VI.GU.L1.02
DEN-SMT/DK