6.2 Tank temperature

Charge difference
Circuit
2
Number of degrees above the desired DHW temperature that will result in
the desired boiler temperature for DHW heating.
1... 50: Number of degrees to be added to the desired DHW
temperature to obtain the desired boiler temperature
for DHW heating.
Start difference
Circuit
2
Set the number of degrees below the desired DHW temperature that will
start the DHW heating (charging).
-50 ... –1: Set the number of degrees.
Danfoss District Energy
ECL Comfort 210 / 310, application A275 / A375
12193
Factory setting
Setting range
1 ... 50 K
15 K
12195
Factory setting
Setting range
–50 ... –1 K
–3 K
Temp.
DHW heating
The desired DHW temperature is related to the tank temperature
sensor.
Example:
Desired DHW temp.:
Start difference:
Result:
The DHW heating starts when the temperature measured by the tank
temperature sensor (upper) is lower than 52 °C.
Temp.
DHW heating
VI.GU.L1.02
Charge difference
Stop difference
Des. DHW temp.
Start difference
Actual DHW temp.
Time
55 °C
-3 K
Start difference
Desired DHW temp.
DHW temp.
Time