Danfoss ECL Comfort 210 Installation Manual page 135

Application a275 / a375
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide
Cut-out (limit for heating cut-out)
Circuit
2
The heating can be switched OFF when the outdoor temperature is
higher than the set value. The valve closes and after the post-run
time, the heating circulation pump stops. 'Temp. min. ' will be
overruled.
The heating system switches ON again when the outdoor
temperature and the accumulated (filtered) outdoor temperature
become lower than the set limit.
This function can save energy.
Set the value for outdoor temperature at which you want the
heating system to switch OFF.
Danfoss District Energy
ECL Comfort 210 / 310, application A275 / A375
12179
Setting range
Factory setting
OFF / 1 ... 50 °C
20 °C
Temp.
Actual outdoor temp.
18 °C
Heating ON
The heating cut-out is only active when the controller mode is in
scheduled operation. When the cut-out value is set to OFF, there is
no heating cut-out.
VI.GU.L1.02
Accumulated outdoor temp.
Heating OFF
Heating ON
Time
DEN-SMT/DK
135

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecl comfort 310

Table of Contents