Danfoss ECL Comfort 210 Installation Manual page 28

Application a275 / a375
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide
A275.3, example d
Boiler ON / OFF control for a direct heating circuit (1), a mixing circuit (2) and a DHW circuit (3). Optional DHW priority. The mixing circuit
(2) is controlled by means of a 4-port mixing valve.
* = pressure relief valve
Heating circuit 2 can alternatively be a floor heating circuit.
At DHW heating P3 is switched ON and the desired boiler temperature is a number of degrees above the desired DHW temperature.
P1 is switched OFF.
Heating circuit 2 can be closed during DHW heating.
Special settings for type A275.3, example d:
Navigation:
Heating circuit (circuit 1)
Circuit 1 must be able to receive a heat demand (desired flow temperature) from circuit 2:
MENU \ Settings \ Application: 'Demand offset'
** This value is added to the heat demand value from circuit 2
Heating circuit (circuit 2)
Circuit 2 must be able to send a heat demand (desired flow temperature) to circuit 1:
MENU \ Settings \ Application: 'Send desired T'
Circuit 2 can be closed during the DHW heating process:
MENU \ Settings \ Application: 'DHW priority'
*** Set 'OFF' when not to be closed, set 'ON' when to be closed
DHW circuit (circuit 3)
DHW heating is managed by pump P3:
MENU \ Settings \ Application: 'Ch.-o. valve / P'
The desired DHW heating temperature must influence the boiler temperature:
MENU \ Settings \ Application: 'Tank, sec./prim.'
28
DEN-SMT/DK
ECL Comfort 210 / 310, application A275 / A375
S 1
M2
S 3
S 5
B1
ECL 210 / (310)
S 4
P 4
S 2
P 1
P 3
VI.GU.L1.02
S 8
S 7
S 6
ID no.:
Recommended setting:
11017
12500
12052
13051
13053
Danfoss District Energy
3 K**
ON
***
ON
OFF

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecl comfort 310

Table of Contents