8.8.9 Communication
Modbus addr.
Circuit
Set the Modbus address if the controller is part of a Modbus network.
1 ... 247: Assign the Modbus address within the stated setting
range.
ECL 485 addr. (master / slave address)
Circuit
This settting is relevant if more controllers are working in the same ECL
Comfort system (connected via the ECL 485 communication bus) and / or
Remote Control Units (ECA 30 / 31) are connected.
0:
The controller works as slave.
The slave receives information about the outdoor
temperature (S1), system time, and signal for DHW
demand in the master.
1 ... 9:
The controller works as slave.
The slave receives information about the outdoor
temperature (S1), system time, and signal for DHW
demand in the master. The slave sends information
about the desired flow temperature to the master.
10 ... 14: Reserved.
15:
The ECL 485 communication bus is active.
The controller is master. The master sends information
about the outdoor temperature (S1) and system time.
Connected Remote Control Units (ECA 30 / 31) are
powered.
The ECL Comfort controllers can be connected via the ECL 485
communication bus to perform a larger system (the ECL 485
communication bus can connect to max. 16 devices).
Each slave must be configured with its own address (1 ... 9).
However, more slaves can have the address 0 if they only have to
receive information about outdoor temperature and system time
(listeners).
Service Pin
Circuit
This setting is only used in connection with set-up of Modbus
communication.
0:
Service pin not activated.
1:
Activation of service pin.
Danfoss District Energy
ECL Comfort 210 / 310, application A275 / A375
38
Setting range
Factory setting
1 ... 247
2048
Setting range
Factory setting
0 ... 15
15
2150
Setting range
Factory setting
0 / 1
1
The total cable length of max. 200 m (all devices incl. the internal ECL
485 communication bus) should not be exceeded.
Cable lengths of more than 200 m may cause noise sensibility (EMC).