Ext. reset
Circuit
This setting is only used in connection with set-up of Modbus
communication.
0:
Reset not activated.
1:
Reset.
8.8.10 Language
Language
Circuit
Choose your language.
166
DEN-SMT/DK
ECL Comfort 210 / 310, application A275 / A375
2151
Factory setting
Setting range
0 / 1
2050
Setting range
Factory setting
English / 'Local'
English
0
Local language is selected during installation. If you want to change to
another local language, the application must be reinstalled. However,
it is always possible to change between the local language and English.
VI.GU.L1.02