Danfoss ECL Comfort 210 Installation Manual page 113

Application a275 / a375
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide
Based on (optimization based on room / outdoor temp.)
Circuit
1
The optimized start and stop time can be based on either room or outdoor
temperature.
OUT:
Optimization based on outdoor temperature. Use this
setting if the room temperature is not measured.
ROOM:
Optimization based on room temperature, if measured.
Total stop
Circuit
1
Decide whether you want a total stop during the saving temperature period.
OFF:
No total stop. The desired flow temperature is reduced
according to:
• desired room temperature in saving mode
• auto saving
ON:
The desired flow temperature is lowered to the set value
in 'Frost pr. ' The circulation pump is stopped but frost
protection is still active, see 'P frost T'.
Cut-out (limit for heating cut-out)
Circuit
1
The heating can be switched OFF when the outdoor temperature is
higher than the set value. The valve closes and after the post-run
time, the heating circulation pump stops. 'Temp. min. ' will be
overruled.
The heating system switches ON again when the outdoor
temperature and the accumulated (filtered) outdoor temperature
become lower than the set limit.
This function can save energy.
Set the value for outdoor temperature at which you want the
heating system to switch OFF.
Danfoss District Energy
ECL Comfort 210 / 310, application A275 / A375
11020
Setting range
Factory setting
OUT / ROOM
OUT
11021
Setting range
Factory setting
OFF / ON
11179
Setting range
Factory setting
OFF / 1 ... 50 °C
20 °C
Desired flow temp. °C
OFF
Desired flow temp. °C
The min. flow temperature limitation ('Temp. min.') is overruled when
'Total stop' is ON.
Temp.
Actual outdoor temp.
18 °C
Heating ON
The heating cut-out is only active when the controller mode is in
scheduled operation. When the cut-out value is set to OFF, there is
no heating cut-out.
VI.GU.L1.02
Total stop = ON
'Frost pr.'
Time
Total stop = OFF
'Frost pr.'
Time
Accumulated outdoor temp.
Heating OFF
Heating ON
Time
DEN-SMT/DK
113

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecl comfort 310

Table of Contents