Application a275 / a375
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide
Optimizer (optimizing time constant)
Circuit
1
Optimizes the start and stop times for the comfort temperature period to
obtain the best comfort at the lowest energy consumption.
The lower the outdoor temperature, the earlier the heating cut-in. The lower
the outdoor temperature, the later the heating cut-out.
The optimized heating cut-out time can be automatic or disabled. The
calculated start and stop times are based on the setting of the optimizing
time constant.
Adjust the optimizing time constant.
The value consists of a two digit number. The two digits have the
following meaning (digit 1 = Table I, digit 2 = Table II).
OFF:
No optimization. The heating starts and stops at the
times set in the schedule.
10 ... 59: See tables I and II.
Pre-stop (optimized stop time)
Circuit
1
Disable the optimized stop time.
OFF:
The optimized stop time is disabled.
ON:
The optimized stop time is enabled.
112
DEN-SMT/DK
ECL Comfort 210 / 310, application A275 / A375
11014
Setting range
Factory setting
OFF / 10 ... 59
OFF
11026
Setting range
Factory setting
OFF / ON
ON
Table I:
Left digit
Heat accumulation of the
1-
2-
3-
4-
5-
Table II:
Dimensioning temperature
Right digit
-0
-1
·
-5
·
-9
Dimensioning temperature:
The lowest outdoor temperature (usually determined by your system
designer in connection with the design of the heating system) at which
the heating system can maintain the designed room temperature.
Example
The system type is radiator, and the heat accumulation of the building
is medium.
The left digit is 2.
The dimensioning temperature is -25 °C, and the capacity is normal.
The right digit is 5.
Result:
The setting is to be changed to 25.
Example: Optimization of Comfort from 07:00 - 22:00
07:00
Optimization start
VI.GU.L1.02
System type
building
light
Radiator
systems
medium
heavy
medium
Floor heating
systems
heavy
Capacity
-50 °C
large
-45 °C
·
-25 °C
normal
·
-5 °C
small
22:00
Schedule
Pre-stop OFF
Pre-stop ON
Optimization stop
Danfoss District Energy
·
·
·