Danfoss ECL Comfort 210 Installation Manual page 70

Application a275 / a375
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide
2.5.5 Electrical connections, Pt 1000 temperature sensors and signals
A275:
Terminal
Sensor / description
S1 Outdoor temperature sensor* ESMT
29 and 30
S2 A275.3 only:
28 and 30
Return temperature sensor,
circuit 2
27 and 30
S3 Boiler temperature sensor**,
circuit 1
S4 A275.3 only:
26 and 30
Flow temperature sensor**,
circuit 2
S5 Return temperature sensor,
25 and 30
circuit 1
S6 A275.2 / A275.3 only:
24 and 30
DHW tank temperature sensor,
circuit 2 / 3
S7 Room temperature sensor***,
23 and 30
circuit 1
S8 A275.3 only:
22 and 30
Room temperature sensor***,
circuit 2
*
If the outdoor temperature sensor is not connected or the
cable is short-circuited, the controller assumes that the
outdoor temperature is 0 (zero) °C.
**
The boiler / flow temperature sensor must always be
connected in order to have the desired functionality. If the
sensor is not connected or the cable is short-circuited, the
motorized control valve closes (safety function).
*** Only for room temperature sensor connection. The room
temperature signal can also be available from a Remote
Control Unit (ECA 30 / 31). See 'Electrical connections, ECA
30 / 31'.
Factory established jumper:
30 to common terminal.
70
DEN-SMT/DK
ECL Comfort 210 / 310, application A275 / A375
Type
(recomm.)
ESM-11 / ESMB /
ESMC / ESMU
ESMU / ESMB
ESM-11 / ESMB /
ESMC / ESMU
ESM-11 / ESMB /
ESMC / ESMU
ESM-11 / ESMB /
ESMC / ESMU
ESM-10
ESM-10
VI.GU.L1.02
Danfoss District Energy