Danfoss ECL Comfort 210 Installation Manual page 124

Application a275 / a375
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide
The heat curves represent the desired flow temperature at different outdoor temperatures and at a desired room temperature of 20 °C.
The small arrows ( ) indicate 6 different outdoor temperature values at which you can change the heat curve.
Temp. max. (flow temp. limit, max.)
Circuit
2
Choose the allowed max. flow temperature for your system.
Adjust the factory setting, if required.
Temp. min. (flow temp. limit, min.)
Circuit
2
Choose the allowed min. flow temperature for your system.
Adjust the factory setting, if required.
124
DEN-SMT/DK
ECL Comfort 210 / 310, application A275 / A375
1.8
2.2
2.6
3.0 3.4
120
110
1.4
100
90
1.0
80
70
0.6
60
50
40
0.2
30
20
10
-30
-20
12178
Setting range
Factory setting
10 ... 150 °C
45 °C
12177
Setting range
Factory setting
10 ... 150 °C
10 °C
-10
0
10
The setting for 'Temp. max. ' has higher priority than 'Temp. min. ' .
The setting for 'Temp. max. ' has higher priority than 'Temp. min. ' .
VI.GU.L1.02
20
Danfoss District Energy