Danfoss ECL Comfort 210 Installation Manual page 164

Application a275 / a375
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide
8.8.7 Raw input overview
Measured temperatures, input status and voltages are displayed.
In addition, a detection of malfunctions can be chosen for activated
temperature inputs.
Monitoring the sensors:
Choose the sensor which measures a temperature, for example the
S5. When the dial is pressed, a magnifying glass
selected line. The S5 temperature is now being monitored.
Alarm indication:
Should the connection to the temperature sensor be disconnected,
short-circuited or the sensor itself be defective, the alarm function
is activated.
In the "Raw input overview" an alarm symbol
defective temperature sensor in question.
Resetting the alarm:
Choose the sensor (S number) for which you want to clear the
alarm. Press the dial. The magnifying glass
disappear.
When the dial is pressed again, the monitoring function is
reactivated.
8.8.8 Display
Backlight (display brightness)
Circuit
Adjust the brightness of the display.
0:
Weak backlight.
10:
Strong backlight.
Contrast (display contrast)
Circuit
Adjust the contrast of the display.
0:
Low contrast.
10:
High contrast.
164
DEN-SMT/DK
ECL Comfort 210 / 310, application A275 / A375
appears in the
is shown at the
and alarm symbols
60058
Setting range
Factory setting
0 ... 10
60059
Factory setting
Setting range
0 ... 10
The temperature sensor inputs have a measuring range from -60 ...
150 ° C.
If a temperature sensor or its connection breaks, the value indication
is " - - ".
If a temperature sensor or its connection is short-circuited, the value
indication is " - - - ".
5
3
VI.GU.L1.02