Danfoss ECL Comfort 210 Installation Manual page 31

Application a275 / a375
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide
A275.3, example g
Boiler ON / OFF control for a direct heating circuit (1) and a mixing circuit (2).
S 1
B1
* = pressure relief valve
Heating circuit 2 can alternatively be a floor heating circuit.
Special settings for type A275.3, example g:
Navigation:
Heating circuit (circuit 1)
Circuit 1 must be able to receive a heat demand (desired flow temperature) from circuit 2:
MENU \ Settings \ Application: 'Demand offset'
** This value is added to the heat demand value from circuit 2
Heating circuit (circuit 2)
Circuit 2 must be able to send a heat demand (desired flow temperature) to circuit 1:
MENU \ Settings \ Application: 'Send desired T'
Danfoss District Energy
ECL Comfort 210 / 310, application A275 / A375
M2
S 3
P 1
S 5
ECL 210 / (310)
S 4
P 4
S 2
VI.GU.L1.02
S 8
S 7
ID no.:
Recommended setting:
11017
3 K**
12500
ON
DEN-SMT/DK
31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecl comfort 310

Table of Contents