Danfoss ECL Comfort 210 Installation Manual page 126

Application a275 / a375
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide
Stop difference
Circuit
2
Number of degrees above or below the desired DHW temperature that will
stop the DHW heating.
–50 ... 50: Set the number of degrees.
126
DEN-SMT/DK
ECL Comfort 210 / 310, application A275 / A375
12194
Setting range
Factory setting
–50 ... 50 K
3 K
Example with positive 'Stop difference' value:
Temp.
DHW heating
Example with negative 'Stop difference' value:
Temp.
DHW heating
VI.GU.L1.02
Stop difference
Desired DHW temp.
Time
Stop difference
Desired DHW temp.
Time