Application - Danfoss ECL Comfort 210 Installation Manual

Application a275 / a375
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide

6.7 Application

ECA addr. (choice of Remote Control Unit)
Circuit
2
Decides the communication with the Remote Control Unit.
OFF:
No Remote Control Unit. Only room temperature sensor,
if any.
A:
Remote Control Unit ECA 30 / 31 with address A.
B:
Remote Control Unit ECA 30 / 31 with address B.
Ch.-o. valve / P (changeover valve / pump)
Circuit
2
Choose whether the DHW heating control is based on a changeover valve
or a pump.
OFF:
Changeover valve
ON:
Pump
Tank, sec. / prim.
Circuit
2
Choose whether the heating of the DHW tank is dependent on the flow
temperature at S3.
OFF:
The DHW tank is heated by means of the S3 temperature.
ON:
The DHW tank is heated separately. The S3 temperature
has no influence on the DHW heating.
Circ. P priority
Circuit
2
Choose whether the DHW circulation pump should be ON during DHW
heating.
OFF:
The DHW circulation pump is switched OFF during DHW
heating.
ON:
The DHW circulation pump is not switched OFF during
DHW heating.
Danfoss District Energy
ECL Comfort 210 / 310, application A275 / A375
12010
Factory setting
Setting range
OFF / A / B
OFF
12051
Setting range
Factory setting
OFF / ON
ON
12053
Factory setting
Setting range
OFF / ON
OFF
12055
Factory setting
Setting range
OFF / ON
OFF
The Remote Control Unit has no influence on the DHW control.
The Remote Control Unit must be set accordingly (A or B).
When the changeover valve is chosen, pump P1 is ON at heating as
well as at DHW heating demand.
When the pump is chosen, pump P1 is ON at heating and OFF at DHW
heating demand.
When the 'Circ. P priority' is set to OFF, the schedule for the DHW
circulation pump is overruled.
VI.GU.L1.02
DEN-SMT/DK
139