If an alarm condition from either 'Upper difference' or 'Lower difference' is
present for a longer time than the set delay (in min.), the alarm function
is activated.
1 ... 99 m: The alarm function will be activated if the alarm
condition remains after the set delay.
Lowest temp.
Circuit
2
The alarm function will not be activated if the desired flow temperature
is lower than the set value.
Danfoss District Energy
ECL Comfort 210 / 310, application A275 / A375
12149
Setting range
Factory setting
1 ... 99 m
10 m
12150
Setting range
Factory setting
10 ... 50 °C
30 °C
Temp.
If the cause of the alarm disappears, the alarm indication and output
also disappear.
VI.GU.L1.02
Flow temp.
Alarm limit
Time
Delay
DEN-SMT/DK
147