Danfoss ECL Comfort 210 Installation Manual page 65

Application a275 / a375
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide
Application A375.1 (up to 4 burner steps)
Double-insulated (two-chamber) transformer
Terminal
Description
19
Phase for alarm and burner B4
18
Alarm (A1)
17
B4
Burner ON / OFF
16
Phase for burner B3
15
B3
Burner ON / OFF
14
Phase for control of pump and burners
13
B2
Burner ON / OFF
12
B1
Burner ON / OFF
11
K1
Control of circulation pump ON / OFF
10
Supply voltage 24 V a.c. - (SN)
9
Supply voltage 24 V a.c. - (SP)
* Relay contacts: 4 A for ohmic load, 2 A for inductive load
Factory established jumpers:
5 to 8, 9 to 14 , L to 5 and L to 9, N to 10
Danfoss District Energy
ECL Comfort 210 / 310, application A275 / A375
VI.GU.L1.02
Max. load
4 (2) A / 24 V a.c.*
4 (2) A / 24 V a.c.*
4 (2) A / 24 V a.c.*
4 (2) A / 24 V a.c.*
4 (2) A / 24 V a.c.*
4 (2) A / 24 V a.c.*
DEN-SMT/DK
65