4 Electrical Wiring
4.5.2 Wire sizes for ES Series
Field minimum wire sizes for the power source
Model
All Indoor Units (1*)
RAS-2HVRN1E
RAS-2.5HVRN1
RAS-3HVRNS
RAS-4HVRNS1E
RAS-5HVRNS1E
RAS-6HVRNS1E
RAS-8HRNSE
RAS-10HRNSE
N O T E
•
(1*): Except RPI-8.0-10.0
•
Follow local codes and regulations when selecting field wires.
•
The above wire sizes marked with (2*) are selected at the maximum current of the unit according to the european
standard, EN60 335-1. Use wires not lighter than the ordinary neoprene (polychloroprene) sheathed flexible
cord (code designation H05RN-F).
•
In the case that the power cables are connected in series, add each unit maximum current and select the wire
sizes in next table.
•
The ground cable size must comply local code: IEC 245, No. 571.
97
SMGB0060 rev. 1- 12/2010
Power Source
Max. Current (A)
230V/1φ/50Hz
400V/3φ/50Hz
Power Source Cable Size
EN60 335-1 (2*)
5
0.75 mm
13
1.5 mm
16
2.5 mm
18
2.5 mm
18/24
4.0 mm
26
6.0 mm
26
20
6.0 mm
23
Transmitting Cable Size
EN60 335-1 (2*)
2
2
2
2
2
0.75 mm
2
2
2
2
0.75 mm
4