Wire Sizes - Hitachi RAS-H(V)RNME-AF Service Manual

Yutaki s series
Hide thumbs Also See for RAS-H(V)RNME-AF:
Table of Contents

Advertisement

4 Electrical wiring

4.3.2 Wire sizes

•  Recommended minimum sizes for field provided wires
Model
Power supply
RWM-2.0FSN3E
1~ 230V 50Hz
RWM-3.0FSN3E
RWM-4.0FSN3E
1~ 230V 50Hz
RWM-5.0FSN3E
3N~ 400V 50Hz
RWM-6.0FSN3E
RWM-8.0FSN3E
3N~ 400V 50Hz
RWM-10.0FSN3E
RAS-2HVRN2
RAS-3HVRNME-AF
RAS-4HVRNME-AF
1~ 230V 50Hz
RAS-5HVRNME-AF
RAS-6HVRNME-AF
RAS-4HRNME-AF
RAS-5HRNME-AF
RAS-6HRNME-AF
3N~400V 50 Hz
RAS-8HRNME-AF
RAS-10HRNME-AF
N O T E
GND: Ground wire
•  Types of switches
Select the main switches in accordance with the following table:
Model
RWM-2.0FSN3E
RWM-3.0FSN3E
RWM-4.0FSN3E
RWM-5.0FSN3E
RWM-6.0FSN3E
RWM-8.0FSN3E
RWM-10.0FSN3E
RAS-2HVRN2
RAS-3HVRNME-AF
RAS-4HVRNME-AF
RAS-5HVRNME-AF
RAS-6HVRNME-AF
RAS-4HRNME-AF
RAS-5HRNME-AF
RAS-6HRNME-AF
RAS-8HRNME-AF
RAS-10HRNME-AF
N O T E
CB: Circuit Breaker
ELB: Earth Leakage Breaker
98
SMGB0070 rev.1 - 08/2011
Power supply
Max.
cable size
Current
(A)
EN60335-1
16
4.0 mm²
16
4.0 mm²
32/11
6.0/2.5 mm²
32/11
6.0/2.5 mm²
32/11
6.0/2.5 mm²
17
4.0 mm²
17
4.0 mm²
11
2.5 mm²
14
4.0 mm²
18
4.0 mm²
26
6.0 mm²
26
6.0 mm²
7
2.5 mm²
11
4.0 mm²
13
4.0 mm²
13
4.0 mm²
17
4.0 mm²
Max. Current
Power supply
(A)
16
1~230V 50Hz
16
32/11
1~230V 50Hz
32/11
3N~400V 50Hz
32/11
17
3N~400V 50Hz
17
11
14
1~230V 50Hz
18
26
26
7
11
13
3N~400V 50 Hz
13,2
17,1
Transmi-
ting Cable
Required
Required
Size
number
number
of wires
of wires
EN60335-
1
2 + GND
2 + GND /
4 + GND
4 + GND
2 +
(*Shiel-
0.75 mm
2
ded ca-
2 + GND
ble)
4 + GND
CB (A)
(no. of poles/A/mA)
20
20
32/15
32/15
2/40/30 - 4/40/30
32/15
20
20
16
25
25
32
32
15
20
20
20
25
Actuator
Required
cable size
number
of wires
EN60335-1
0.75 mm
2 + GND
2
ELB
2/40/30
4/40/30
2/40/30
4/40/30

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents