8 Troubleshooting
14
Alarm code
The RUN LED flickers and "ALARM" is displayed on the remote control switch.
The unit number, the alarm code and the unit code are alternately displayed on the set temperature section.
The unit number and the alarm code are displayed on the display of the outdoor unit PCB.
This alarm code is displayed when the thermistor is short-circuited (less than 0.24 kΩ) or cut (greater than 840 kΩ)
during the cooling process or the heating process. The system is automatically restarted when the fault is removed.
Phenomenon
Faulty gas piping thermistor
Faulty PCB
238
SMGB0060 rev. 1- 12/2010
Abnormal operation of the thermistor for the indoor unit heat exchanger gas pipe temperature
Cause
Fault
Incorrect connection
(gas piping thermistor)
Check item
Check the resistance
Check the connection
Replace PCB and
check the operation
Action
(Turn OFF the main switch)
Replace the thermistor if faulty
Repair the wiring and connections
Replace PCB if faulty