10 Servicing
6
Remove the CN5A connector on the control PCB of the electrical box.
7
Hold and disconnect the coil of the expansion valve.
The expansion valve coil is equipped with a lock mechanism.
Ensure that the coil is locked when replacing.
1. One terminal cover screw.
2. Side cover.
3. Seven side cover screws.
4. Three front cover screws.
N O T E
DO NOT touch electrical components while the LED1 (Red) is ON to avoid electrical shock. Wait until the LED
turns off.
¿
Removing electrical components
Removing Electrical Box
1
Remove the pipe cover following
2
Remove three (3) fixing screws and remove the upper cover.
3
Remove the electrical box cover.
4
Remove one (1) fixing screw and remove the terminal cover.
5
Disconnect all the wiring connected to the control PCB.
6
Remove two (2) screws which fix the electrical box.
7
Pull up and remove the electrical box.
400
SMGB0060 rev. 1- 12/2010
1. Expansion valve coil.
2. Expansion valve body.
Removing pipe
cover, see on page 395.