Outdoor Units Ras-(4-6)H(V)Rnm1E - Hitachi RAS-5HVRNM1E Service Manual

Hide thumbs Also See for RAS-5HVRNM1E:
Table of Contents

Advertisement

10 Servicing
Remove the noise filter by clamping the top of the holder (6 portions) with a pincher.
Identify the terminal numbers with mark band. When reassembling, the terminals have to be connected to the
correct numbers . If incorrectly connected, malfunctions or damages will occur.

10.2.2 Outdoor units RAS-(4-6)H(V)RNM1E

¿
Removing service cover
N O T E
Remove the main parts according to the following procedures.
To reassemble perform the procedures in reverse.
To prevent contamination of the refrigerant with water or foreign particles, do not expose open to
atmosphere for long periods.
If necessary, seal pipe ends using caps or tape.
1
Remove the four (4) fixing screws.
2
Slide the service cover downward and remove it.
3
Pay attention of not falling off the service cover.
1. Service cover.
¿
Remove air outlet grille
1
Remove the eight (8) fixing screws.
2
Lift the air outlet grille holding the lower parts.
3
Release the extruded hook of the air outlet grille from the
shroud.
1. Air outlet grille.
2. Shroud.
366
SMGB0060 rev. 1- 12/2010
1
2
2
1

Hide quick links:

Advertisement

Table of Contents
loading