Hitachi RAS-5HVRNM1E Service Manual page 322

Hide thumbs Also See for RAS-5HVRNM1E:
Table of Contents

Advertisement

8 Troubleshooting
2. Inverter module checking procedure
Internal Circuit of Rectified Part of DIP-IPM
Non-faulty if [1] – [8] are checked and satisfied. (Measure with 1 kΩ range of a tester.)
N O T E
DO NOT use a digital tester
1. Touch [+] of the tester to DIP-IPM 52C terminal, and [-] to
DIP-IPM R, S terminals to measure the resistance. Normal if
all three terminals have 1 kΩ or greater.
2. Contrary to [1], touch [-] of the tester to DIP-IPM 52C
terminal, and [+] to DIP-IPM R, S terminals to measure the
resistance.
Normal if all three terminals have 100 kΩ or greater.
3. Touch [-] of the tester to [-] of DIP-IPM DMI (soldered part),
and [+] of the tester to DIP-IPM R, S terminals to measure the
resistance.
Normal if all three terminals have 1 kΩ or greater
4. Contrary to [3], touch [+] of the tester to [-] of DIP-IPM DMI,
and [-] of the tester to DIP-IPM R, S terminals to measure the
resistance.
Normal if all three terminals have 100 kΩ or greater
1. Tester.
2. Contact with specified terminals to measure.
Internal Circuit of Rectified Part of Inverter Module (Cont.)
314
SMGB0060 rev. 1- 12/2010
2
1