Hitachi RAS-5HVRNM1E Service Manual page 227

Hide thumbs Also See for RAS-5HVRNM1E:
Table of Contents

Advertisement

8 Troubleshooting
Phenomenon
Disconnected wires, insufficient
contacting or incorrect connection
Faulty PCB (PCB1 for the control,
PCB for the inverter)
Incorrect wiring
219
SMGB0060 rev. 1- 12/2010
Cause
Between control PCB, inverter PCB
and FANM
Power source wiring for the outdoor
unit
Disconnected wires to PCB
Faulty PCB
Disconnected wires;
insufficient contacting
Incorrect wiring
Check item
Check the continuity of wires.
Check for looseness of the
connection screws. Check the
connection No.
Check the connections
Check the continuity.
Check for looseness of connection
screws
Check the connection nos.
Action
(Turn OFF the main switch)
Replacing wires, repairing,
tightening screws and incorrect
wiring
Repair the wiring connections
Replace PCB if faulty
Replacing wires, repairing,
tightening screws
Correctly connect the wires
8