Refrigerant Charge Quantity - Hitachi RAS-5HVRNM1E Service Manual

Hide thumbs Also See for RAS-5HVRNM1E:
Table of Contents

Advertisement

3 Piping work and
refrigerant charge

3.2.7 Refrigerant charge quantity

¿
Refrigerant charge quantity for IVX series
Outdoor units has been charged with refrigerant for ℓ(m) of actual piping length. An additional refrigerant charged is required
in systems with actual piping length longer than ℓ(m).
1
Determine an additional refrigerant quantity according to the following procedure, and charge it into the system.
2
Record the additional refrigerant quantity to facilitate service activities thereafter.
C A U T I O N
When charging refrigerant accurately measure refrigerant to be charged.
Overcharging or undercharging of refrigerant can cause compressor trouble.
In case of actual piping length less than 5 m, consult your distributor.
Outdoor unit Factory Refrigerant charge (Wo Kg) is the next:
O/U MODEL
RAS-3HVRNME
RAS-4H(V)RNM1E
RAS-5H(V)RNM1E
RAS-6H(V)RNM1E
1
Refrigerant shall be added if L is longer than the chargeless length shown in the table above.
Calculate the additional amount as follows:
A. 30 m.
B. 8 m.
C. 8 m.
Chargeless Length ℓ: for 4HVRNM1E is 30 m according to
the table before.
Additional Correction Value P : for 4HVRNM1E, "0.06"
according to the table above.
Additional Charge amount W will be:
W = (L-ℓ) x P
Example: W
= (46-30) x 0.06 = 0.96 (kg)
1
2
Charge the amount W calculated by point 1.
3
Setting of pipe length DSW.
DSW2 setting will be required only when the refrigerant pipe
length is shorter than 5 m or longer than 30 m. Pipe length
setting shall be performed as shown below.
(The ■ side in the DIP switch show the position.)
Factory setting
Piping length between 5 m and ℓ(m)
57
SMGB0060 rev. 1- 12/2010
Wo (Kg)
Chargeless Length ℓ(m)
2.4
3.9
3.8
3.8
DSW2 on outdoor PCB1
Factory setting
Pipe Length 5 m or shorter
Additional Charge Factor (P)
30
30
30
30
Factory setting
Pipe Length 30 m or longer
3
0.04
0.06
0.06
0.06

Hide quick links: