REMEHA Quinta 30 Technical Information page 23

High-effi ciency condensing boiler
Table of Contents

Advertisement

Warning: changing factory defaults without reference to the tables contained in this
manual may result in incorrect operation.
- To delete the service code press the 'reset'-key once
- If no keys are pressed over a 15 minute period the service code will delete auto-
matically
Code
Description
Flow temperature set point
$
during forced part load
High limit temperature set point
%
Fan speed at full load (HTG)
^
Fan speed at part load (HTG
&
and DHW)
Modulation start point DT (F/R)
*
Interface selection (control
(
option)
DHW cut-in DT
B
Fan speed at full load (DHW)
C
Intern
D
N/a
E
N/a
F
Forced part load time after start
G
(HTG)
Fan speed at start
H
DHW control stop or boiler
I
modulation set point (based on
parameter #)
DHW control option
J
Variable speed pump
L
HTG cut in DT
N
Setting range
20 - 90ºC
90 – !0 (= 110°C)
10 – 60 hundreds
10 – 60 hundreds
05 - 30 ºC
00 internal (Chronotherm
control only)
01 external interface
10 – 05 read 1 - 5 °C
06 read 10 °C
07 read 15 °C
08 read 20 °C
10 – 60 hundreds
May not be changed!
00 – 15 minutes
May not be changed!
00 – 30 °C
00 = Three way valve
(port A = HTG,
port B = DHW)
01 = DHW pump
02 = inverted three way
valve (port A = DHW,
port B = HTG)
23
n/a
1) (= -10°C) – 20 °C
Preset
Q30
80
)0 (=100)*
53
12
25
01
05
53
00
)0 (=100)*
25
03
25
20
00
)3
03