Flow Temperature Set Point During Forced Part Load ($); High Limit Thermostat (%); Fan Speed At Full Load Htg (^) - REMEHA Quinta 30 Technical Information

High-effi ciency condensing boiler
Table of Contents

Advertisement

N/a
F
Forced part load time after start
G
(HTG)
Fan speed at start
H
DHW control stop or boiler
I
modulation set point (based on
parameter #)
DHW control option
J
Variable speed pump
L
HTG cut in DT
N
N/a
O
Boiler type
P
Intern
T
Maximum delay time
U
Start point for 0 Volt analog
Q
signal
End point for 10 Volt analog
Y
signal
Intern
_
Table 09
Settings service level
* Note: see Par. 6.1.4 for values over two digits

6.6.1 Flow temperature set point during forced part load ($)

Adjustable from 20 to 90°C, factory default 80°C
This value will prevent the flow temperature exceeding this temperature during the part
load time.

6.6.2 High limit thermostat (%)

Adjustable from 90 to 110°C (!0), factory default 100°C ()0).
This value sets the high limit temperature at which the boiler will shut down in a lock
out condition requiring manual intervention.
Note: this parameter will have an effect on the minimum flow rate requirement,
see Par. 7.4.7.

6.6.3 Fan speed at full load HTG (^)

Adjustable from 20% to 100% output (= 1200 to 5300 rpm), factory default 53
(100%). This value sets the maximum output of the boiler.
00 – 15 minutes
May not be changed!
00 – 30 °C
00 = Three way valve
(port A = HTG,
port B = DHW)
01 = DHW pump
02 = inverted three way
valve (port A = DHW,
port B = HTG)
n/a
1) (= -10°C) – 20 °C
May not be changed!
May not be changed!
00 – 99 minutes
5) (= -50) – 50 °C
50 – (( (=299) °C
24
25
03
25
Remeha Quinta 30
20
00
)3
03
10
74
01
15
00
)0 (=100)*
10