Boiler Temperature Control - REMEHA Quinta 30 Technical Information

High-effi ciency condensing boiler
Table of Contents

Advertisement

Fig. 13 Gasmodul control box
00W4H7900018

8.2.4 Boiler temperature control

The Remeha Quinta 30 has electronic temperature control with flow and return tempe-
rature sensors. The flow temperature can be adjusted between 20 and 90°C.
8.2.5 High limit temperature protection
The high limit temperature protection device switches off and locks out the boiler when
the flow temperature exceeds the high limit set point (adjustable). When the fault is
corrected, the boiler can be restarted by using the 'reset'-key on the control panel.
8.2.6 Low-water protection (flow and content)
The Remeha Quinta 30 is supplied with a low-water protection on the basis of tempe-
rature measurement, see Fig. 22, Boiler sensor resistance/temp graph. By modulating
back at the moment that the water flow threatens to fall too low, the boiler is kept ope-
rating for as long as possible. In the event of low flow (F/R ∆T = 45°C), the boiler will
shut off and not lockout (ref. Par. 6.4).
If the boiler is fired dry, it will go to high temperature lock out, failure code 1*
8.3 External connections
All external connections (except rematic
strip, located in the instrument box at the bottom of the boiler, accessed by loosening
the two screws, see Fig. 14 and Fig. 15.
2945 C3) are made on the 24 way terminal
®
43