Remeha Quinta 30
Fig. 20
Flue gas measure point
05.W3H.79.00066
Correct gas/air setup:
16.1. Connect the flue gas analyser, ensuring the connections are gas tight.
16.2. Run the boiler at full-load by pressing 'm'- and [+]-keys simultaneously.
16.3. When full-load speed is reached, check values against the table and adjust if
necessary using the screw on the venturi (see Fig. 21).
Full load*
Part load
Fig. 21 Setting screws
05.W3H.79.00064
*) Full load setting screw can also be reached through the top of the casing by
removing a little plug.
50