11 INSPECTION AND SERVICING INSTRUCTIONS
11.1
General
The Remeha Quinta 30 has been designed to need minimum maintenance, but to
ensure optimum efficiency we advise that once a year the boiler should be checked
and if necessary cleaned and reset.
All service and maintenance must be carried out by a qualified Engineer with the rele-
vant training and certification (ie CORGI - ACOPS - etc.).
11.2
Annual Inspection
The annual inspection of the Remeha Quinta 30 as follows:
- check combustion characteristics, see Table 16.
- clean the condensate siphon (refill with clean water)
- check for leaks (water side, flue gas side and gas soundness)
- check flue and air inlet system is clear and gas/water tight
- check system pressure
- check control settings
- check ionisation level, minimum 4 µA dc (ionisation measurement in Volts between
terminal 4 and earthing, 1V dc ≡ 1 µA dc) If ionisation level < 4 µA dc, check:
- CO
at both part and full flame
2
- is flame core visible?
- is flame geometry stable?
- ignition probe earthing
- temperature sensors for loss current (humidty on sensors)
Visual check of ignition/ionisation probes:
- if white oxydes show, use sand paper or screwdriver for cleaning
- check geometry and distance between both probes, i.e. 3 to 4 mm.
- clean and re-set the ignition electrode
Note: If flue gas temperature is more than 30°C above the boiler return water tempe-
rature the heat exchanger must be cleaned see Par. 11.3.
58
Remeha Quinta 30