6.5.2 Pump run on time HTG (@)

Pump run on time can be adjusted (Please refer to installation contractor)
- Press the 'm' -key until the digit ! (with dot) appears in the 'code'-display.
- Press the 's'-key until the digit @ (with dot) appears in the 'code'-display.
- Set the required value, using the [+] and [-]-keys.
- Press the 'e'-key to store the new value (value will flash twice).
- Press the 'reset'-key to return to operating mode.
Note: For continuous pump operation use manual override, see Par. 6.1.3.
Code
t
@
00
@
Xx
Table 07
Pump run on time HTG
6.5.3 DHW temperature set point (3)
The DHW temperature is adjustable from 20 to 75°C (factory default 55°C). Only with
Broag DHW priority sensor.
- Press the 'm' -key until the digit ! (with dot) appears in the 'code'-display.
- Press the 's'-key until the digit # (with dot) appears in the 'code'-display.
- Set the required value, using the [+] and [-]-keys.
- Press the 'e'-key to store the new value (value will flash twice).
- Press the 'reset'-key to return to operating mode.
Remark: there are further adjustments available on service level. Please refer to your
service engineer or contractor (see Par. 6.6.7).

6.5.4 Boiler control setting (A)

The boiler is factory set to option 11 (HTG modulating or on/off with DHW on)
To change the control option:
- Press the 'm' -key until the digit ! (with dot) appears in the 'code'-display.
- Press the 's'-key until the digit A (with dot) appears in the 'code'-display.
- Set the required X and Y values as listed below in using the [+] and [-]-keys.
- Press the 'e'-key to store the new value (value will flash twice).
- Press the 'reset'-key to return to operating mode
With the 'code'- display showing A - the t-display will indicate the method of boiler
control in the first segment x[and the option to turn the HTG and DHW on or off
in the second segment [y. By using codes from the table below a series of control
options are available
Description
Pump runs on for 10 seconds
Pump runs on for 1 to 15 minutes (xx = 01 to 15)
21