Viessmann Vitodens 222-F B2TA Installation And Service Instructions Manual page 98

Hide thumbs Also See for Vitodens 222-F B2TA:
Table of Contents

Advertisement

Code 2
"Boiler"/group 2
Coding in the delivered condition
06:...
Maximum limit of the boil-
er water temperature, de-
faulted in °C by the boiler
coding card
0d:0
Do not adjust
0E:0
Do not adjust
13:1
Do not adjust
14:1
Do not adjust
15:1
Do not adjust
21:0
No service interval (hours
run) selected.
23:0
No interval for burner
service
24:0
"Service" not shown on
display
28:0
No burner interval igni-
tion
2E:0
Do not adjust
2F:0
Venting program/fill pro-
gram disabled
30:1
Internal variable speed
circulation pump (auto-
matic adjustment)
98
(cont.)
Possible change
Pause time set permanent-
ly (specified by boiler cod-
ing card)
06:20
Maximum limit adjustable
to
within the ranges specified
06:127
by the boiler
21:1
The number of hours run
to
before the burner should
21:100
be serviced is adjustable
from 100 to 10 000 h.
One adjusting step ≙
100 h
23:1
Interval adjustable from 1
to
to 24 months
23:24
24:1
"Service" is shown on dis-
play (the address is auto-
matically set and must be
manually reset after a serv-
ice has been carried out)
28:1
Time interval adjustable
to
from 1 h to 24 h. The burner
28:24
is force-started for 30 s at a
time (only when operating
with LPG).
2F:1
Venting program enabled
2F:2
Fill program enabled
30:0
Internal circulation pump
without variable speed
(e.g. temporarily for serv-
ice)