Viessmann Vitodens 222-F B2TA Installation And Service Instructions Manual page 84

Hide thumbs Also See for Vitodens 222-F B2TA:
Table of Contents

Advertisement

Code 1
"Heating circuit ..."/group 5
Coding in the delivered condition
Weather-compensated/room temperature hook-up
b0:0
Only for heating circuit
with mixer and remote
control:
Heating mode/reduced
mode: Weather-compen-
sated (only for weather-
compensated control
units)
Economy function room temperature
b5:0
Only for heating circuit
with mixer and remote
control:
No room temperature-de-
pendent heating circuit
pump logic function (only
for weather-compensa-
ted control units)
Parameter ad-
With heating circuit pump logic function:
dress b5:...
Heating circuit pump "OFF"
1
RT
2
RT
3
RT
4
RT
5
RT
6
RT
7
RT
8
RT
84
(cont.)
> RT
+ 5 K
actual
set
> RT
+ 4 K
actual
set
> RT
+ 3 K
actual
set
> RT
+ 2 K
actual
set
> RT
+ 1 K
actual
set
> RT
actual
set
> RT
– 1 K
actual
set
> RT
– 2 K
actual
set
Possible change
b0:1
Heating mode: weather-
compensated.
Reduced mode: With room
temperature hook-up
b0:2
Heating mode: With room
temperature hook-up
Reduced mode: Weather-
compensated
b0:3
Heating mode/reduced
mode: With room tempera-
ture hook-up
b5:1
Heating circuit pump logic
to
function, see the following
b5:8
table
Heating circuit pump "ON"
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
+ 4 K
set
+ 3 K
set
+ 2 K
set
+ 1 K
set
set
– 1 K
set
– 2 K
set
– 3 K
set

Advertisement