Troubleshooting
Fault codes
(cont.)
Dis-
Const.
played
fault
code
bC
bd
126
Weath.-
System char-
comp.
acteristics
X
Control mode
without remote
control
X
Control mode
without remote
control
Cause
Measures
Communica-
Check connec-
tion error, re-
tions, cable, coding
mote control
address "A0" in
Vitotrol heat-
group "Heating
ing circuit 1
circuit..."5/ and re-
(without mix-
mote control con-
er)
figuration (see
page 166).
For wireless re-
mote controls:
Check connec-
tions, place remote
control unit close to
the boiler
Communica-
Check connec-
tion error, re-
tions, cable, coding
mote control
address "A0" in
Vitotrol heat-
group "Heating
ing circuit 2
circuit..."/5 and re-
(with mixer)
mote control con-
figuration (see
page 166).
For wireless re-
mote controls:
Check connec-
tions, place remote
control unit close to
the boiler