Viessmann Vitodens 222-F B2TA Installation And Service Instructions Manual page 105

Hide thumbs Also See for Vitodens 222-F B2TA:
Table of Contents

Advertisement

"Heating circuit ..."/group 5
Coding in the delivered condition
No room temperature-de-
pendent heating circuit
pump logic function (only
for weather-compensa-
ted control units)
Parameter ad-
With heating circuit pump logic function:
dress b5:...
Heating circuit pump "OFF"
1
RT
2
RT
3
RT
4
RT
5
RT
6
RT
7
RT
8
RT
Coding in the delivered condition
C5:20
Electronic minimum flow
temperature limit 20 °C
(only in operation with
standard room tempera-
ture; only for weather-
compensated control
units)
C6:74
Electronic maximum flow
temperature limit 74 °C
(only for weather-com-
pensated control units)
d3:14
Heating curve slope =
1.4
d4:0
Heating curve level = 0
(cont.)
> RT
+ 5 K
actual
set
> RT
+ 4 K
actual
set
> RT
+ 3 K
actual
set
> RT
+ 2 K
actual
set
> RT
+ 1 K
actual
set
> RT
actual
set
> RT
– 1 K
actual
set
> RT
– 2 K
actual
set
Possible change
Heating circuit pump "ON"
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
Possible change
C5:1
Minimum limit adjustable
to
from 1 to 127 °C (limited by
C5:127
boiler-specific parameters)
C6:10
Maximum limit adjustable
to
from 10 to 127 °C (limited
C6:127
by boiler-specific parame-
ters)
d3:2
Heating curve slope adjust-
to
able from 0.2 to 3.5 (see
d3:35
page 70)
d4:–13
Heating curve level adjust-
to
able from –13 to 40 (see
d4:40
page 70)
Code 2
+ 4 K
set
+ 3 K
set
+ 2 K
set
+ 1 K
set
set
– 1 K
set
– 2 K
set
– 3 K
set
105