Fault Codes - Viessmann Vitodens 222-F B2TA Installation And Service Instructions Manual

Hide thumbs Also See for Vitodens 222-F B2TA:
Table of Contents

Advertisement

Troubleshooting

Fault codes

Dis-
Const.
played
fault
code
0F
10
X
18
X
19
X
20
X
122
Weath.-
System char-
comp.
acteristics
Control mode
X
Controls as if
the outside
temperature
were 0 °C
X
Controls as if
the outside
temperature
were 0 °C
X
Controls as if
the outside
temperature
were 0 °C
X
Regulates with-
out flow tem-
perature sen-
sor (low loss
header)
Cause
Measures
Service
Service required
"0F" is only
displayed in
Note
the fault histo-
After servicing, se-
ry
lect code "24:0".
Short circuit,
Check outside tem-
outside tem-
perature sensor
perature sen-
(see page 139)
sor
Lead break,
Check outside tem-
outside tem-
perature sensor
perature sen-
(see page 139)
sor
Communica-
Check wireless
tion error,
connection (place
wireless out-
wireless outside
side tempera-
temperature sen-
ture sensor
sor close to the
wireless base sta-
tion). Log off out-
side temperature
sensor then log on
again. Replace if
required (see
"Wireless base sta-
tion" installation
and service in-
structions)
Short circuit,
Check low loss
system flow
header sensor (see
temperature
page 140)
sensor