Commissioning, inspection, maintenance
Further details regarding the individual steps
All coding addresses in the table are listed in the "General" group.
Boiler control unit
LON
Subscriber no. 1,
Code "77:1".
Control unit is fault
manager,
Code "79:1".
Control unit transmits
the time,
Code "7b:1".
Control unit transmits
outside temperature,
Set code "97:2".
Viessmann system
number,
Code "98:1".
LON subscriber fault
monitoring,
Code "9C:20".
Carrying out a LON subscriber check
The subscriber check is used to test
communication with the system devices
connected to the fault manager.
Preconditions:
■ The control unit must be programmed
as fault manager (code "79:1" in the
"General" group).
■ The LON subscriber number must be
programmed in all control units.
■ The LON subscriber list in the fault
manager must be up to date.
74
Vitotronic 200-H
LON
Subscriber no. 10,
Code "77:10".
Control unit is not
fault manager,
Code "79:0".
Control unit receives
the time,
Set code "81:3".
Control unit receives
outside tempera-
ture,
Set code "97:1".
Viessmann system
number,
Code "98:1".
LON subscriber fault
monitoring,
Code "9C:20".
Vitotronic 200-H
LON
Subscriber no. 11,
Set code "77:11".
Control unit is not
fault manager,
Code "79:0".
Control unit receives
the time,
Set code "81:3".
Control unit receives
outside tempera-
ture,
Set code "97:1".
Viessmann system
number,
Code "98:1".
LON subscriber fault
monitoring,
Code "9C:20".
Service menu:
1. Press OK and
approx. 4 s.
2. "Service functions"
3. "Subscriber check"
4. Select subscriber (e.g. subscriber 10).
5. Start the subscriber check with "OK".
(cont.)
Vitocom
Subscriber
no. 99.
Device is fault
manager.
Device re-
ceives the
time.
—
—
—
simultaneously for