Viessmann Vitodens 222-F B2TA Installation And Service Instructions Manual page 130

Hide thumbs Also See for Vitodens 222-F B2TA:
Table of Contents

Advertisement

Troubleshooting
Fault codes
(cont.)
Dis-
Const.
played
fault
code
E1
X
E3
X
E4
X
E5
X
E6
X
130
Weath.-
System char-
comp.
acteristics
X
Burner in a fault
state
X
Burner in a fault
state
X
Burner blocked Fault, 24 V
X
Burner blocked Fault, flame
X
Burner blocked System pres-
Cause
Measures
Ionisation
Check gap be-
current too
tween ionisation
high during
electrode and
calibration
burner gauze as-
sembly (see
page 52).
In open flue opera-
tion, prevent high
incidence of dust in
the combustion
air.
Press reset button
R
Heat transfer
Ensure adequate
too low during
heat transfer.
calibration.
Press reset button
Temperature
R
limiter has
shut down
Replace control
supply volt-
unit
age
Replace control
amplifier
unit
Top up with water
sure too low