Coding in the delivered condition
E1:1
Do not adjust
E2:50
With remote control:
No display correction for
the actual room tempera-
ture (only for weather-
compensated control
units)
E5:0
Do not adjust
E6:...
Only for heating systems
without a heating circuit
with mixer:
Maximum speed of the in-
ternal variable speed
heating circuit pump in %
of the max. speed in
standard mode. Value is
specified by boiler-specif-
ic parameters (only for
weather-compensated
control units)
E7:30
Only for heating systems
without a heating circuit
with mixer:
Minimum speed of the in-
ternal variable speed
heating circuit pump:
30 % of the max. speed
(only for weather-com-
pensated control units)
E8:1
Only for heating systems
without a heating circuit
with mixer:
(cont.)
Possible change
d8:3
Heating program change-
over via input DE3.
E2:0
Display correction –5 K
to
to
E2:49
Display correction –0.1 K
E2:51
Display correction +0.1 K
to
to
E2:99
Display correction +4.9 K
E6:0
Maximum speed adjusta-
to
ble from 0 to 100 %
E6:100
E7:0
Minimum speed adjustable
to
from 0 to 100 % of the max-
E7:100
imum speed
E8:0
Speed subject to the set-
ting in coding address
"E7"
Code 2
107