Viessmann Vitodens 222-F B2TA Installation And Service Instructions Manual page 128

Hide thumbs Also See for Vitodens 222-F B2TA:
Table of Contents

Advertisement

Troubleshooting
Fault codes
(cont.)
Dis-
Const.
played
fault
code
Cd
CF
d6
X
d7
X
d8
X
dA
128
Weath.-
System char-
comp.
acteristics
Control mode
X
Control mode.
No communi-
cation via LON
X
Control mode
X
Control mode
X
Control mode
X
Control mode
without room
influence
Cause
Measures
Communica-
Check connections
tion error,
and Vitocom 100
Vitocom 100
(see separate in-
stallation and serv-
ice instructions).
Without Vitocom
100: Set code
"95:0" in group
"General"/1
Communica-
Check LON com-
tion error,
munication module
LON commu-
and replace if re-
nication mod-
quired.
ule
If no LON commu-
nication module is
installed, set code
"76:0" in group
"General"/1
Input DE1 re-
Remove fault at
ports a fault at
appliance con-
extension
cerned
EA1
Input DE2 at
Remove fault at
extension
appliance con-
EA1 reports a
cerned
fault
Input DE3 at
Remove fault at
extension
appliance con-
EA1 reports a
cerned
fault
Short circuit,
Check room tem-
room temper-
perature sensor,
ature sensor,
heating circuit 1
heating circuit
1 (without
mixer)