Fault codes
(cont.)
Dis-
Const.
played
fault
code
F3
X
F8
X
F9
X
FA
X
FC
X
Fd
X
Weath.-
System char-
comp.
acteristics
X
Burner in a fault
state
X
Burner in a fault
state
X
Burner in a fault
state
X
Burner in a fault
state
X
Burner in a fault
state
X
Burner in a fault
state and addi-
tional fault b7 is
displayed
Troubleshooting
Cause
Measures
Flame signal
Check ionisation
is already
electrode and con-
present at
necting cable.
burner start
Press reset button
R
Fuel valve
Check gas train.
closes too
Check both control
late
paths.
Press reset button
R
Fan speed
Check fan, fan con-
too low during
necting cables and
burner start
power supply;
check fan control.
Press reset button
R
Fan not in idle
Check fan, fan con-
state
necting cables and
fan control.
Press reset button
R
Gas train faul-
Check gas train.
ty, faulty mod-
Check flue sys-
ulation valve
tem.
control or flue
Press reset button
gas path
R
blocked
Boiler coding
Insert the boiler
card is miss-
coding card.
ing
Press reset button
R
Replace control
unit if fault persists
135