Viessmann Vitodens 222-F B2TA Installation And Service Instructions Manual page 100

Hide thumbs Also See for Vitodens 222-F B2TA:
Table of Contents

Advertisement

Code 2
"DHW"/group 3
Coding in the delivered condition
60:20
During DHW heating, the
boiler water temperature
is max. 20 K higher than
the set DHW tempera-
ture
62:2
Circulation pump with
2 min run-on time after
cylinder heating
63:0
Without auxiliary function
for DHW heating (only for
constant temperature
control units)
65:...
Do not adjust (Informa-
tion on the type of diverter
valve, specified by the
boiler coding card)
6C:100
Set speed, internal circu-
lation pump for DHW
heating 100 %
6F:...
Max. heating output for
DHW heating in %, speci-
fied by the boiler coding
card
71:0
DHW circulation pump:
"ON" in accordance with
the time program (only for
weather-compensated
control units)
72:0
DHW circulation pump:
"ON" in accordance with
the time program (only for
weather-compensated
control units)
73:0
DHW circulation pump:
"ON" in accordance with
the time program (only for
weather-compensated
control units)
100
(cont.)
Possible change
60:5
The difference between the
to
boiler water temperature
60:25
and the set DHW tempera-
ture is adjustable from 5 to
25 K
62:0
Circulation pump without
run-on time
62:1
Run-on time adjustable
to
from 1 to 15 min
62:15
63:1
Auxiliary function: 1 x daily
63:2
Every 2 days to every
to
14 days
63:14
63:15
2 x daily
6C:0
Set speed adjustable from
to
0 to 100 %
6C:100
6F:0
Max. heating output for
to
DHW heating adjustable
6F:100
from min. heating output to
100 %
71:1
"OFF" during DHW heating
to set value 1
71:2
"ON" during DHW heating
to set value 1
72:1
"OFF" during DHW heating
to set value 2
72:2
"ON" during DHW heating
to set value 2
73:1
During time program
to
"ON" from once per hour
for 5 min to

Advertisement