Further details regarding the individual steps
Checking the burner gasket and burner gauze assembly
Check burner gasket A and burner
gauze assembly E for possible damage
and replace if required.
B
1. Remove electrodes B.
2. Undo two retaining clips C on ther-
mal insulation ring D and then
remove thermal insulation ring D.
Commissioning, inspection, maintenance
F
E
2x
3. Undo two Torx screws and remove
burner gauze assembly E with gas-
ket F.
4. Insert new burner gauze assembly
E with new gasket F and secure.
Torque: 5.0 Nm.
(cont.)
D
A
2x
C
51