Troubleshooting
Fault codes
(cont.)
Dis-
Const.
played
fault
code
EF
X
F0
X
F1
X
F2
X
134
Weath.-
System char-
comp.
acteristics
X
Burner in a fault
state
X
Burner blocked Internal fault
X
Burner in a fault
state
X
Burner in a fault
state
Cause
Measures
Flame is lost
Check gas supply
immediately
(gas pressure and
after it has
gas flow switch).
formed (dur-
Check balanced
ing the safety
flue system for flue
time)
gas recirculation.
Check ionisation
electrode (replace
if necessary):
■ Distance to burn-
er gauze assem-
bly (see page 52)
■ Contamination of
electrode
Press reset button
R
Replace control
unit
Flue gas tem-
Check heating sys-
perature limit-
tem fill level. Vent
er has re-
the system.
sponded
Press reset button
R after flue system
has cooled down
Temperature
Check heating sys-
limiter has re-
tem fill level. Check
sponded
circulation pump.
Vent the system.
Check temperature
limiter and con-
necting cables.
Press reset button
R