Preparing For Assembly - Varta element 3 Instruction Manual

Hide thumbs Also See for element 3:
Table of Contents

Advertisement

The current sensor is designed for top hat rail mounting and for a
maximum current of 50 A per phase. For installation, the sensor
board points towards the sub-distributor. For installation direction,
see also Figure 12.
Phases L1, L2, L3 must be identical for building connection,
current sensor and terminal block. This means, phase L1 of the
building connection leads through opening L1 of the current
sensor to terminal L1 on the terminal block in the storage cabinet.
Connect the current sensor supplied with the sensor cable to the
energy storage system. See the current measurement socket in
Figure 14.
For the connection arrangement, see figures 1a/1b and 2a/2b
in the attachment.
8.4

Preparing for assembly

Make sure that the substrate is adequately load-bearing, have the
structural analysis checked if necessary. The preconditions for
mechanical assembly at the installation location are as follows:
an even surface
any unevenness compensated
a wall without lines running in front or inside
The technical requirements for the storage cabinet connection
must be satisfied by a qualified electrician certified by VARTA
Storage GmbH.