Preparing The Electrical Connection - Varta element 3 Instruction Manual

Hide thumbs Also See for element 3:
Table of Contents

Advertisement

8.3

Preparing the electrical connection

Mortal danger from electric shock!
Before working on electrical equipment,
disconnect the fuses devices, secure to prevent
reconnection and check the equipment has been
DANGER!
disconnected from the power supply.
Risk of injury and property damage if the
electrical connections are incorrectly
installed!
CAUTION!
The fuse upstream of the energy storage system
must be three-pole. This satisfies the
requirements for an isolator.
Protect the device connection on the energy
storage system with a type B, three-pole, 16-A
fuse.
Observe the shut-off conditions in accordance
with VDE 0100-410.
Install LS and FI for connecting the consumers
entitled to the emergency power supply.
Never connect the energy storage system
without PE and N.
Subject to alteration! Updated 11/2015
45