Installation Location - Varta element 3 Instruction Manual

Hide thumbs Also See for element 3:
Table of Contents

Advertisement

Property damage from the effects of weather
with indoor installations.
Install the storage cabinet only inside buildings!
NOTICE!
8.1.1

Installation location

Provision must be made for a minimum footprint of 70 cm x 55 cm
(width x depth) at the installation location. The distance to the
adjacent installations must be approx. 5 cm to the right and
approx. 10 cm to the left. A clear space of approx. 120 cm deep is
required in front of the device, since all installation and
maintenance work is carried out via the front door. The screws for
opening the storage cabinet on the left next to the front door must
be accessible.
A minimum clearance of 30 cm must be left above the storage
cabinet. No objects may be placed on the top of the storage
cabinet. The clearance between the wall and the rear of the
cabinet must remain free to enable cooling air to escape from the
device unhindered.
A minimum of 30 m³ is recommended for the room in which
VATRA element 3/6 is installed. A continuous air exchange must
essentially be guaranteed, if necessary via forced ventilation,
such as windows, air conditioning system, ventilation system or
similar. The clearance to the ventilation system must be at least
100 cm.
The room temperature must always be between 5 °C and
30 °C, ideally approx. 18 °C.
Recommended: well-ventilated room without external
heat sources.
Subject to alteration! Updated 11/2015